Channel: 225A HOML2225 Subfeed Lug Block in 200A main breaker panel at service entrance feeds 200A breaker subpanel w/ 40' 4/0 AL SER cable in buried conduit - Home Improvement Stack Exchange
Browsing index pages (3 articles)

225A HOML2225 Subfeed Lug Block in 200A main breaker panel at service...

From this site, and others, I understand that NEC allows powering a Square D Homeline 200A sub-panel from a HOML2225 225A Subfeed Lug Block installed in a 200A Homeline main service panel, using 4/0 AL...

View Article


Answer by manassehkatz-Moving 2 Codidact for 225A HOML2225 Subfeed Lug Block...

Your service is only 200A. So first of all, it is pointless to send more than 200A to a subpanel because even if everything in the main panel was totally off and never used, you still couldn't use more...

View Article


Answer by nobody for 225A HOML2225 Subfeed Lug Block in 200A main breaker...

You may not use 125A feed-through lugs (and corresponding wire) in a panel fed by 200A service. That would be prone to dangerous overloading. You can do some things sort of like that with conductor...